warninginvestigatingINC-002 · opened 02:20 HST

KAZE-02 below wind-adjusted expectation

KAZE-02 · site generation · ≈1.5 kW shortfall now; ≈13 kWh over 24h (estimated)

Device readings & records

Observed facts

Synthetic
  • Device readingKAZE-02 output2.6 kW vs 4.1 kW2 min ago · measured
  • DerivedPeer turbinesKAZE-01 4.7 kW · KAZE-03 4.4 kW in same wind2 min ago · estimated
  • Device readingSite wind speed7.2 m/s at WX-012 min ago · measured
  • DerivedExpected output modelSite-specific baseline (synthetic model)2 min ago · synthetic-model
  • RecordLast maintenanceService visit 94 days ago · no findings logged94 d ago · measured
KAZE-02 observedKAZE-02 wind-adjusted expected (synthetic)KAZE-01KAZE-03
Inference · not confirmed

Possible explanations

Illustrative heuristic, not a calibrated probability

The shortfall may be associated with the following. A bearing or mechanical fault is NOT diagnosed; only on-site inspection can confirm.

Power metering or sensor inaccuracy
0.40 heuristic
Conflicting
None recorded
Local wind shading or turbulence at KAZE-02
0.30 heuristic
Mechanical wear (not confirmed — needs on-site inspection)
0.30 heuristic
Agent proposal

Recommended safe next steps

  1. Sensor/metering calibration check against a reference reading.
  2. Schedule an on-site visual and mechanical inspection.
  3. Continue monitoring output vs peers for 48 h.

Remote stop or restart is not available. Turbine control requires a separately modelled safety role and capabilities.

Raw readings (advanced)
SourceMetricValueQualityTimestamp (HST)
KAZE-02EV-K2-OUT2.6 kW vs 4.1 kW wind-adjusted baselinemeasured08:38
KAZE-01EV-K2-PEERSKAZE-01 4.7 kW · KAZE-03 4.4 kW in same windestimated08:38
WX-01EV-WIND7.2 m/s at WX-01measured08:38
KAZE-02EV-K2-BASESite-specific baseline (synthetic model)synthetic-model08:38
KAZE-02EV-K2-MAINTService visit 94 days ago · no findings loggedmeasured14:40